Title: Parametric study of induced draft counter flow rectangular cooling tower based on exergy analysis
Authors: Aggarwal, Gaurav
Kachhwaha, S S
Mishra, R S
Keywords: Draft equation
Exergy analysis
Induced draft cooling tower
Parametric study
Issue Date: Apr-2010
Publisher: CSIR
Abstract:  This study presents development of a simple and efficient mathematical model, in which energy, draft and pressure equations are solved simultaneously. Model was validated with experimental data collected from an induced draft counter flow rectangular cooling tower of a refrigeration plant (capacity, 220 tonnes) in a dairy industry at Ambala (India). Model predictions and experimental data match satisfactorily. In a parametric study, wet bulb temperature of inlet air plays a significant role on air and water outlet temperatures, evaporation loss, fan power, thermal efficiency, exergy destruction and second law efficiency.
Description: 284-292
URI: http://hdl.handle.net/123456789/7714
ISSN: 0975-1084 (Online); 0022-4456 (Print)
Appears in Collections:JSIR Vol.69(04) [April 2010]